Performance Under Pressure

Feb. 9, 2024
In this case study, a 2007 Ford Edge is experiencing a misfire under certain conditions.

A good friend of mine, Michael, was recently faced with a 2007 Ford Edge experiencing a misfire under certain driving conditions. After some preliminary data evaluation, he hypothesized that the drivability symptom stemmed from a fault in the vehicle’s ignition system.

By systematically placing the vehicle’s engine under sustained load, the misfire fault would present itself readily and always seemed to occur on cylinder No. 2. Considering the ignition system’s configuration, it was not prudent to swap the coils from cylinder to cylinder (a common technique to see if the misfire fault moves along with the coil). The coils of bank No. 1 reside under the intake manifold (Figure 1).

 

 

With the idea of an ignition system fault in mind, Michael monitored the suspect coil’s control circuit with a digital storage oscilloscope (DSO), along with a non-suspect coil for comparison (Figure 2). After capturing the data during the misfire condition, the only anomaly Michael noticed was a difference in the coil-oscillation section of the ignition event.

 

It seems (whether the misfire was present or not) that the coil oscillations are missing from the suspect coil’s ignition event. Two questions come to mind:

  • What do the missing coil oscillations mean? 
  • Is it the cause of the misfire?

Preliminary data

This is where Michael reached out to me to evaluate the ignition events and see if I could offer some insight. Again, a coil swap is just what the doctor ordered but considering the coils reside beneath the intake manifold, it is not a gamble worth taking at this point. Let's see what the data has to offer us (Figure 3).

 

The ignition event occurs because of a transfer of energy. But this energy is derived from magnetism.  

A magnetic field is created when electrical current flows through the primary windings of the ignition coil. 

However, the magnetic field that develops over time (what we refer to as “dwell”) must dissipate instantaneously when the electrical current stops flowing through the primary windings of the ignition coil. When that occurs, and through the function of the step-up transformer (the ignition coil, itself) a spark should discharge.

This spark contains a finite amount of energy. A properly designed and properly functioning ignition system should produce a spark not only capable of igniting the air/fuel (A/F) mixture under all operating conditions; there should be some reserve energy remaining. This reserve energy will be seen dissipating as coil oscillations, ringing out over time (Figure 4). 

 

The data doesn’t lie

With all the information in front of us, and the desired information not yet obtained, we are faced with deciding how to proceed. Here are some bullet points of what we know to be factual, and I will ask all of you, diligent readers, for your input: 

  • The No. 2 cylinder misfires under load 
  • Preliminary data points to an ignition system fault  
  • Comparative ignition captures show a variation in the coil oscillations between cylinders 
  • The coils are housed under the intake manifold

Given this information, what would you do next?

  1. Replace all six ignition coils 
  2. Replace the No. 2 ignition coil only 
  3. Commit to intake removal and swapping coils for diagnostic purposes 
  4. Obtain a common amperage waveform of all coils

 

SOLVED:(December 2023, Motor Age) 2013 Honda Crosstour, “check gas cap” message  

What would you recommend doing next, given the data bullet points in last month’s challenge?     

   

  Given this information, what would you do next?   

  1. Smoke test the EVAP system 
  2. Replace the fuel cap because it’s inexpensive 
  3. Replace PCM 
  4. Monitor FTP, vent solenoid, and purge valve with a lab scope during failure 

  

For those of you who chose answer No. 4, congratulations! According to the data, smoke testing EVAP system would not yield any leak. The FTP sensor signal remained stable under natural vacuum testing conditions. These conditions are a lot more stringent than a smoke test, meaning, if the natural-vacuum test passes, the EVAP system will most likely pass a smoke test. For this same reason, replacing a fuel cap due to low cost would still be foolish because a leak is not present.  

Although replacing a PCM may be the correct step (assuming there was a logic error), doing so is premature because there are still unanswered questions. Monitoring the FTP, vent solenoid, and purge valve simultaneously with a lab scope will not only verify the functionality of the components working as a system but will also demonstrate the failure when it occurs.  

The purge solenoid was the root cause of the fault (Figure 5). At times, it would fail to seal during monitor criteria conditions. A DTC never set because this component would never fail during the natural-vacuum leak detection that occurred during key-off testing conditions. This fault would only occur on the road (when the engine compartment was hot).  

  

Be sure to read April's Motor Age issue for the answer to this month’s challenge and what was discovered!  

Sponsored Recommendations

ADAS Case Study: From 10 Calibrations a Month to Over 10 A Day

Originally published by Vehicle Service Pros, March 26, 2024

Snap-on Training: Approach to Intermittent Problems

Snap-on's live training sessions can help you develop your own strategy for approaching vehicle repair.

Snap-on Training: ADAS Level 2 - Component Testing

The second video for Snap-on's comprehensive overview of Advanced Driver Assistance Systems (ADAS), covering the fundamental concepts and functionalities essential for automotive...

Snap-on Training: Intro to ADAS

Snap-on's training video provides a comprehensive overview of Advanced Driver Assistance Systems (ADAS), covering the fundamental concepts and functionalities essential for automotive...

Voice Your Opinion!

To join the conversation, and become an exclusive member of Vehicle Service Pros, create an account today!